KYN28A-12 Switchgear Metal-Clad Retractabilis
KYN28A-12 (etiam scriptum KYN28-12) est apparatus interruptivus AC metallicus armatus ad usum internum, qui ad systemata AC trifasica ad tensiones nominatas 3,6 kV, 7,2 kV et 12 kV (50/60 Hz) aptatur. Hic apparatus secundum normas IEC 62271-200 et IEC 62271-100 exacte constructus est, atque est electio praestantissima in stationibus electricis publicis, in distributione electricitatis industriali, et in plantis energiae renovabilis per totum Orientem Medium.
Apparatus electricus usus est in totum compartimentatum inclosure metallicum divisum in quattuor camerae isolatas: camerae busbar, camerae interruptoris circuitus, camerae cabilis, et camerae instrumentorum tensionis infimae. Haec architectura quattuor-compartimentorum impedit propagationem defectuum et permittit tutam manutenationem dum tabulae adiacentes manent energizatae.
- Praevisio
- Applicationes
- Technical Data
- Services
- Controlus qualitatis
- Producta Recommandata
KYN28-12A Withdrawable Metal-Clad Medium Voltage Switchgear - 12kV
KYN28-12 (etiam KYN28A-12 appellatus) est interior armatus extrahibilis commutator electricus AC in metalla inclusus pro systematibus trivoltinis nominibus 3.6 kV, 7.2 kV et 12 kV ad 50 Hz vel 60 Hz. Ad normas IEC 62271-200 et IEC 62271-100 constructus, est frequentissimus tabulatus medi-voltaticus in stationibus electricis publicis, distributionibus industrialibus et generationibus renovabilibus in Medio Oriente, Africa, Russia et Europa Orientali.
FOUR-COMPARTMENT ARCHITECTURE
Hoc clausum in quattuor separatas cellulas dividitur per terrae-metallum barrières: busbar, interruptorem circuitus, caleum, et instrumentum voltatis infimae. Hoc est quod veram constructionem metallo-inclusam a tabulis metallo-inclusis minus pretiosis distinguit: defectus in una cellula ad alteram non propagari potest, et aequipe mantinentiae in cellula calei operari potest dum busbar adhuc vivit. Est etiam conditio praevia pro classificatione arcus interni, quia via liberationis pressionis pro singulis cellulis designata est.
TROLLEY INTERRUPTORIS EXTRAHIBILIS
Vacuum circuit breaker portatur in carro manuale cum tribus positionibus definitis: Servitium, Experimentum, et Isolatum. Interruptor ad experimentum rachetari potest et pro verificando protectione operari, dum contactus principales isolantur, aut omnino extrahi et sub una hora substitui sine de-energisatione busbar. Interbloccatio mechanica sequentiam tutam in hardware, non in procedura, imponit: interruptor non rachetari potest dum interruptor terrae clausus est, interruptor terrae non claudere potest dum interruptor clausus est, et porta compartimenti cavi non aperiri potest nisi circuitus terrae sit.
SPECIFICATUS PRO RETE DESTINATIONIS
- Medius Oriens et Africa: rete 11 kV. Projecta SEC Arabiae Sauditarum ad 60 Hz verificata sunt; omnes alii mercatus regionis ad 50 Hz operantur.
- Russia et CIS: rete 10 kV, disponibilis in versionibus climaticis GOST 15150 cum calefactione anti-condensationis et unguento mechanismi frigus-resistente.
- Europa Orientalis: rete 10 kV secundum normam harmonizatam EN 62271-200.
IEC rates this equipment at a +40 C ambient. Gulf substations routinely operate at 50–55 C, so we supply the derating calculation and, where required, uprated busbar cross-section or forced ventilation rather than letting the panel run beyond its verified temperature rise.
Configurationis
Incomer, bus-section, bus-riser, feeder, PT and metering panels combine into a complete lineup. IP4X is standard with IP54 available for dusty and coastal sites. The panel accepts VS1-12, VD4 and 3AH5 breaker trolleys, allowing standardisation across a mixed installed base.
Applicationes principali
- Utility secondary distribution substations on 10 kV and 11 kV networks — the highest-volume application across all four target regions.
- Industrial plant main incomer and feeder switchboards: cement, steel, mining, textiles, food processing.
- Oil, gas and petrochemical facility power distribution, including onshore processing and tank farms.
- Water treatment and desalination plants — a major segment across Saudi Arabia, UAE, Kuwait and Qatar.
- Substationum mediī voltātūs ad colligendōs solārem photovoltaicum et ventī molīnōs, quae ad punctum connēxionis cum rete dēferunt.
- Substationum in aedificiīs commericiālibus altīs, hospitālibus, aeropōrtibus et centris datōrum, ubi casus salūtis electricae exigit tabulam segregātam.
- Commūtātiō ad āctiōnem generātiōnis renovābilis et propriīs locīs.
FUNCTIONES TABULAE TYPICAE
Tabula introductōria cum metrō et prōtectione; tabula sectionis omnibus, pro operatiōne cum duōbus omnibus separātīs; tabulae egressūs ad transformātōrēs, mōtōrēs et sub-distribūtiōnem; tabula cum transformātōre voltātūs et arresterē clādīs; cubiculum metrīcum ad mensūram redituum.
Congruentia Regionalis
- Arabiā Saūdītān, Emirātūs Arābēs Ūnītī, Qaṭar, Kuwait, Ōmān, Īrāq: distribūtiō 11 kV, alta temperātūra ambientis et pulvis aerius sunt fāctorēs praecipuī dēsignī. Proiecta Arabiāe Saūdītānae requirunt verificātiōnem ad 60 Hz.
- Nīgeria, Kenia, Ghāna, Tanzānia, Ugandā, Āfrica Meridiōnālis: distribūtiō 11 kV cum fluctuātiōnibus latīs voltātūs retis et capacitate manūtenentiōnis locālis limitātā, quae robur interclūsiōnum et praesentiam rērum reservārum faciunt dēcīsīvam.
- Russia, Kazakhstan, Belarus et CIS: rete 10 kV, saepe cum neutro isolato vel terrato per resonantia, quae idoneam selectionem factoris tensionis VT et qualificatum ad temperaturas minimas exigunt.
- Polonia, Romania, Bulgaria, Hungaria, Serbia: rete 10 kV secundum EN 62271-200.
Non idoneus pro
Installatio directa extra aedificium aut abri containeris, et applicationes supra 12 kV — specificare KYN28-24 pro rete 20 kV et 22 kV, aut classis 40.5 kV pro systematibus 35 kV.
DATA TECHNICA — KYN28-12 / KYN28A-12
| CATEGORIA | Item | Specificatie |
| Conformitas | Standards | IEC 62271-200, IEC 62271-100, GB/T 11022 |
| Electrical Ratings | Voltage aestimatum | 12 kV (3.6 kV / 7.2 kV optionale) |
| Frequentia censita | 50 Hz / 60 Hz | |
| Tensio retinenda ad frequentiam potestatis (1 min) | 42 kV | |
| Impulsus fulminis toleratus (BIL) | 75 kV in vertice | |
| Currens normalis nominalis — omnibus | 1250 / 1600 / 2000 / 2500 / 3150 / 4000 A | |
| Currens normalis nominalis — distributio | 630 / 1250 / 1600 A | |
| Currentus interruptus curtocircuitus | 25 kA / 31.5 kA | |
| Currentus formans curtocircuitus | 63 kA / 80 kA ad cacumen | |
| Currentem brevi tempore sustinendam | 25 kA / 31,5 kA pro 4 s | |
| Sequentia operativa | O – 0.3s – CO – 180s – CO | |
| Construction | Gradus Protectionis | Norma IP4X; IP54 optabilis |
| Classificatio arcus interni | IAC A FL (secundum IEC 62271-200) | |
| Theca | Accipiter laminatus frigide, coopertus pulvere RAL 7035 | |
| Materies Busbar | Cuprum; stannum-platum optabile | |
| Compartimenta | Busbar / CB / Cable / LV instrument | |
| Breaker compatibility | VS1-12, VD4-12 (ABB), 3AH5 (Siemens) | |
| Introitus funis | Bottom entry standard; top entry optional | |
| Dimensiones | Largitudo tabulae | 800 mm (≤1250A) / 1000 mm (≥1600A) |
| Altitudo Laminarum | 2200 mm | |
| Profunditas Pannellorum | 1500 mm | |
| Pondus (circa) | 800–1200 kg per panel | |
| Status servitii | Ambiens Temperature | −10 °C to +40 °C; up to +55 °C with derating |
| Altitudo | ≤1000 m standard; ≤2000 m on request | |
| Humiditas relativa | Daily average ≤95% | |
| Seismic qualification | Praesto Ad Petitionem |
Optiones
IP54 enclosure upgrade | anti-condensation heater and thermostat | forced ventilation for high ambient | arc fault detection and rapid tripping | motorised racking for remote operation | GOST 15150 climatic version (UHL) for CIS supply | 60 Hz verification for Saudi Arabia | tin-plated busbar | cable compartment extension for multiple cables per phase
PRE-SALES ENGINEERING
- Revision of single-line diagram and development of panel schedule from your load list.
- Equipment selection verified against destination grid: 11kV/13.8kV/22kV/33kV (Middle East, Africa), 6kV/10kV/35kV (Russia & CIS), 10kV/20kV/35kV (Eastern Europe). Saudi Arabian projects are designed and verified at 60 Hz.
- Ambient derating study. IEC 62271-1 rates equipment at +40 °C; we recalculate continuous current for 50–55 °C Gulf conditions or supply GOST 15150 climatic versions (UHL1 to −60 °C) for CIS sites.
- Short-circuit and protection coordination check against your upstream fault level.
- 2D/3D general arrangement drawings, foundation and cable-entry layouts before production release.
MARKET ACCESS AND DOCUMENTATION
We prepare the technical dossier behind the approval, which is normally the longest item on the project critical path:
- Arabia Saudita: certificatum producti SASO / SABER (PCoC) et certificatum pro singulis expeditionibus (SCoC); auxilium ad approbationem materialis SEC et examinatio acceptationis fabricae testata.
- UAE / Qatar / Kuwait / Oman: fasciculi documentorum pro registratione suppeditantis DEWA, approbatione materialis KAHRAMAA, submissione MEW et approbatione producti Oman DCRP (obligatorium ex anno 2018).
- Iraq: certificatum conformitatis ICIGI per corpora inspectionis a COSQC nominata.
- Africa: PC et SC SONCAP pro Nigeria, PVoC KEBS (via Iter A/B/C) pro Kenya, certificata TBS / UNBS / GSA alibi. Inspectio ante expeditionem et sigillatio contineris coordinata cum agente nominato.
- Russia et CIS: certificatio GOST R pro apparatibus mediis tensionis, cum auxilio representantis autorisati EAEU.
Notandum est quod prima approbatio utilitatis saepe biennium ad duodecim menses occupat, secundum auctoritatem. Hoc incipere debet simul cum collocatione ordinis, non post.
ACCEPTATIO FABRILIS ET DELIVERIA
- Probae regularis pro omni tabula secundum IEC 62271-200: resistentia ad tensionem frequentialis, resistentia circuitus principalis, operatio mechanica, verificatio interbloccorum, functio circuitus auxiliaris.
- FAT (Testis Acceptationis a Fabrica) testificatus ab cliente vel tertio partibus (SGS, BV, TUV, Intertek) disponibilis ad petitionem. Proiecta SEC in Arabia Saudita requirunt FAT testificatum ab ingeniore SEC.
- Impacatio exportatoria maritima: cassa ex ligno compresse, desiccans, barriera contra umorem, indicatores impulsus et inclinationis pro confectionibus MV.
- Series documentorum: relationes probationum, certificata probationum typicarum, schemata generalia et diagrammata, manuale operationis et manutenctionis, index partium reservarum, index impacationis. Manuales disponibiles sunt Anglice, Russice, Gallice et Arabice.
Post-Venditio
- Supervisio commissionis et directio installationis in loco, per viam remotam aut per missionem ingeniarii.
- Formatio operatorum et manutenctorum, in loco aut per viam electronicam.
- Index partium reservarum biennalis recommendatus, citatus una cum ordinatione — modus efficacissimus unicus ad evitandos moras longiores in mercatis ubi partes locales non sunt disponibiles.
- Responsum technicum intra 24 horae; res consumibiles (contactus, insulatoria, bobinae, mechanismi) in magazino retinentur ad expeditam expeditionem.
- Garantia: 18 mensium ab expeditione aut 12 mensium ab inauguratione, quod prius exspirat. Condicio protracta negotiari potest pro conventionibus quadramentalibus.
VERIFICATIO DESIGNIS ET EXAMEN SPECIFICUM
- Examina specifica secundum IEC 62271-200 pro interruptoribus metallicis inclusis AC: tolerantia tensionis frequentialis et impulsum fulminis, correntis toleratae brevi tempore et maxime, incrementum temperaturae, capacitas connexiones faciendi et dissolvendi, durabilitas mechanica, et gradus protectionis.
- Classificatio arcus interni (IAC) per experimentum verificata, cum valvulis liberationis pressionis et canalis exhaustus probatis ut arcum continerent et operatorem protegerent. Haec est qualificatio distincta a tolerantia dielectrica et in documentis licitationis expressim petenda est.
- Raportus de examinatio ab tertio facto ex KEMA, ASTA, CESI aut TUV disponibiles. Nota quod certificatum ASTA signatur ab observatore ASTA qui responsabilitatem pro raportu suscipit, quare utilitas et procuratio EPC eum aliter tractant quam proprium fabricantis documentum de examinatio.
Controlus materiae ingressae
- Interruptores vacui, mechanismi operantes, relais protectionis et transformatoribus instrumentorum solum ex fornitoribus qualificatis accepti secundum certificatum conformitatis.
- Barrae cupreae verificatae pro conductivitate, sectione transversali et spissitudine plating.
- Componentes insulationis epoxy testatae pro descensu partiali in receptione.
- Spissitudo laminae ferreae et spissitudo pelliculae pulveris-coat per singulos lotos verificatae; finitio normalis RAL 7035.
Inspectio in cursu productionis
- Examinatio dimensionum et quadratura carchasiae post fabricationem.
- Verificatio torque barrae bus cum clavibus calibratis, annotata pro singulo iunctura.
- Verificatio wiring punctum-ad-punctum contra schemata approbata ante energisationem.
- Ordo interlock mechanicus in omni tabula probatus: interruptor non potest in locum rapi cum interruptore terrae clauso; interruptor terrae non potest claudi cum interruptore clauso; ostium compartimenti cavi non potest aperiri nisi terra fiat.
TESTINGUS ORDINARIUS — OMNIS TABULA, NULLUM SAMPLING
- Tensio retinenda ad frequentiam potentiae in circuitibus principalibus et auxiliaribus.
- Mensura resistentiae circuitus principalis, comparata ad basim designi.
- Testus operationis mechanicus per totam seriem Servitium / Testus / Isolatus.
- Testus functionum protectionis et controlis, incl. trip et close ab relecto.
- Verificatio gradus protectionis et pelliculae picturae.
- Ad singulam tabulam datur relatio testus ordinarii numerata.
TRACEABILITAS ET SYSTEMA
- Systema gestionis qualitatis ISO 9001.
- Tractabilitas numeri serialis a pane finito retro ad interruptorem vacuum, mechanismum et partem isolantem batch.
- Registra testuum retinentur et recuperabilia sunt pro tempore garantis et ultra, quod magni momenti est cum utilitas quaestionem post annos in usu movet.
QUALIFICATIO AMBIENTALIS
Normales gradus IEC supponunt ambientem +40 °C. Ubi destinatio magis exigit, nos verificamus secundum: experimentum incrementi temperaturae in ambiente elevato pro projectis in Golfo, experimentum pulveris salis pro installationibus littoralibus, et versiones climaticae GOST 15150 cum verificatione functionis ad temperaturas infimas pro deploymento in CIS.